ALLMAG 5000 IO-Link Electromagnetic Flow Meter
A compact magnetic flow meter with IO-Link, a colour TFT display and two configurable outputs, for monitoring, transmitting and batching conductive liquids.

Key Features of the ALLMAG 5000 IO-Link Electromagnetic Flow Meter
IO-Link communication
IO-Link V1.1 on output 1, COM3 bit rate and 1.1 ms minimum cycle time (MIS), with SIO mode and block parameterisation.
Two configurable outputs
Each output can be 4 to 20 mA, 0 to 20 mA, 0 to 10 V or 2 to 10 V, an NPN, PNP or push-pull switch, or a pulse or frequency output.
Dosing and batching
Output 2 runs a dosing output while output 1 acts as the start, stop and reset input.
A grand totaliser and a resettable totaliser are both kept.
Bidirectional measuring
Flow is measured in both directions.
Colour display, touch keys
A 1.4" 128 × 128 TFT display rotates in 90° steps, changes colour on limit violations, and the four optical touch fields work with gloves.
Temperature as well (MIM)
The MIM has a Pt1000 temperature sensor, so one device reports flow and liquid temperature.
ALLMAG 5000 Technical Specifications
Tap a group to filter the IO-Link flow meter specifications, or show them all.



- IO-LinkCommunicationplus 4 to 20 mA
- 0.01 to 650 l/minMIM rangeG¼ to G2
- DN80 / DN100MIS flanged3" and 4"
- IP67Protection
| Specification | Details |
|---|---|
| Measured medium | Conductive liquids, minimum conductivity ≥ 20 µS/cm, maximum viscosity 70 mm²/s |
| MIM ranges | G¼: 0.01 to 1 l/min; G½: 0.03 to 3 or 0.04 to 10 l/min; G¾: 0.1 to 25 or 0.2 to 50 l/min; G1: 0.2 to 50 or 0.4 to 100 l/min; G2: 1.5 to 350 or 3 to 650 l/min |
| MIS sizes | DN80 (3") and DN100 (4") flanged |
| Accuracy | MIM: < ±(0.8% of reading + 0.5% of full scale); MIS: < ±(0.5% of reading + 0.3% of full scale); repeatability ±0.2% of full scale |
| Response time | Flow t90 < 250 ms (alarm and pulse output); MIM temperature t90 < 20 s |
| Outputs | 2 configurable outputs: 4 to 20 mA, 0 to 20 mA, 0 to 10 V, 2 to 10 V, NPN/PNP/push-pull switch, pulse, frequency (2 kHz overflow) |
| IO-Link | Output 1 in IO-Link mode; IO-Link V1.1, COM3, 1.1 ms minimum cycle time, SIO mode, block parameterisation, max. cable 20 m (MIS) |
| Dosing function | Dosing output on OUT2; start/stop and reset control input on OUT1 |
| Display and set-up | 1.4" TFT, 128 × 128 pixels, rotatable in 90° steps; 4 optical touch fields usable with gloves |
| MIM wetted parts | 316L stainless steel housing, fittings and electrodes, PEEK insulation, FKM seals (others on request) |
| MIS wetted parts | Steel ASTM A105 connection, paint coated (C4M); NBR liner; Hastelloy C276 electrodes |
| Pressure and temperature | MIM: 16 bar (230 psi), media -20 to +70 °C; MIS: 16 bar, media -10 to +70 °C; remote MIM versions with 2 m cable up to 85 °C (PVC) or 140 °C (ETFE) |
| Straight pipe | MIM: 3 × DN upstream, 2 × DN downstream; MIS: 5 × DN upstream, 3 × DN downstream; any mounting position |
| Protection | IP67 |
| Supply | 19 to 30 V DC, max. 200 mA |
| Electrical connection | M12x1 plug, 4-pin |
Figures from the Allpronix ALLMAG 5000 MIM and MIS datasheets. Confirm the model, size and options for your application before ordering.
Download Data SheetHow does the ALLMAG 5000 work?
Step by step:
The measurement does not depend on density, viscosity or temperature. Output 1 can be set to IO-Link so the PLC reads flow, totals and status digitally, while output 2 stays free for an alarm or a batching signal.
Where the ALLMAG 5000 is used
Typical applications for this IO-Link flow meter, from the manufacturer's documentation.
- 01Batching and dosingFilling and dosing with the built-in batching function and external start input.
- 02Water treatment and tappingWater treatment, water tapping, watering and waste water treatment.
- 03Leak detectionWater distribution networks, for leakage detection and management.
- 04Filtration and machinesReverse osmosis and ultrafiltration systems, cooling water and industrial machines.
How the ALLMAG 5000 compares
The highlighted row is this instrument. Tap any other name to open its page.
| Instrument | Principle | Range | Output | Supply | Protection |
|---|---|---|---|---|---|
| Electromagnetic | |||||
| ALLMAG 4000 electromagnetic flow meter | Electromagnetic | DN10 to DN2000, up to 15 m/s | 4 to 20 mA, pulse, RS485, HART | 100 to 240 V AC or 24 V DC | IP65 compact, IP68 remote |
| ALLMAG 5000 IO-Link electromagnetic flow meter | Electromagnetic | 0.01 l/min (G¼) to DN100 flanged | IO-Link, 4 to 20 mA, pulse, switch | 19 to 30 V DC | IP67 |
| Coriolis | |||||
| Coriolis mass flow meter | Coriolis | DN3 to DN150, up to 360 t/h | 2 × 4 to 20 mA, pulse, Modbus, HART | 24 V DC or 220 V AC | IP67 |
| Flow sensor | |||||
| ALL-005 programmable thermal flow sensor | Thermal (calorimetric) | 0.04 to 3 m/s liquids, 2 to 100 m/s air | 2 × switch, 4 to 20 mA, IO-Link | 18 to 30 V DC | IP65 / IP67 |
| Differential pressure | |||||
| Itabar and deltaflow pitot flow tubes | Differential pressure | DN40 up to DN12000 | Via the DP transmitter | Passive sensor | Stainless steel, up to 400 °C (IBF) |
From Selection to a Working Signal in Your Control System
A flow meter is only as useful as the signal that reaches the control room. Proplant PCE handles the steps around the instrument as well as the instrument itself.
Application review
We check the liquid or gas, pipe size, flow range, process conditions and output before recommending a meter.
Supply
Instruments from the brands on this page, with datasheets and calibration certificates for your engineering file.
Installation
Mechanical installation, earthing, cabling and termination by our E&I team.
Integration
Signal wiring and configuration into your PLC or SCADA, including Siemens systems.
What to tell us so we can recommend an instrument
Tick off what you already know. We will check the ALLMAG 5000 against your conditions, or suggest a better fit from our range.
Other flow instruments to consider
ALLMAG 5000 FAQ
What is the difference between the MIM and the MIS?
The MIM is a compact all-metal meter with threaded connections from G¼ to G2 and a temperature sensor. The MIS is a flanged meter in DN80 and DN100 for medium-sized water lines.
What does IO-Link add?
Output 1 can run as an IO-Link port, so the PLC reads flow, totals and settings digitally over a standard 3-wire sensor cable, and the meter can be parameterised remotely.
Can it still give a 4 to 20 mA signal?
Yes. Both outputs can be set to 4 to 20 mA, 0 to 20 mA, 0 to 10 V or 2 to 10 V, or to switch, pulse or frequency outputs.
Can it batch or dose?
Yes. A dosing function uses output 2 as the dosing output and output 1 as the start, stop and reset input.
What liquids can it measure?
Conductive liquids of at least 20 µS/cm and up to 70 mm²/s viscosity, such as water and many water-based process liquids.
Can Proplant PCE help me choose the right model?
Yes. Send us the liquid, pipe size, flow range and the signal your PLC needs, and we will recommend the model and range.