Acromag 981EN, 982EN and 983EN 12-Channel Discrete Ethernet I/O
12-channel discrete Ethernet I/O modules: inputs on the 981EN, outputs on the 982EN and both on the 983EN, communicating by Modbus TCP/IP or EtherNet/IP with no software needed.

Key Features of the Acromag 98xEN
Input, output or both
981EN 12 inputs, 982EN 12 outputs, 983EN 12 bidirectional channels.
Discrete inputs
12 active-low, buffered inputs, 0 to 35 V DC, TTL-compatible threshold with about 100 mV hysteresis.
Sinking outputs
12 open-drain MOSFET outputs, 0 to 35 V DC, 0 to 500 mA per channel continuous.
Failsafe outputs
Three selectable modes on loss of communication: off, last state or pre-defined.
Modbus TCP or EtherNet/IP
-4012 Modbus TCP/IP, -6012 EtherNet/IP with a PCCC object for legacy PLCs, conformance tested.
No software
Configured from a built-in web page.
Acromag 98xEN Technical Specifications
Tap a group to filter the digital to Ethernet module specifications, or show them all.

- 12Channelsdiscrete
- 500 mAOutput currentper channel
- 1500 V ACIsolation3-way
- -25 to 70 °COperating temperature
| Specification | Details |
|---|---|
| Models | 981EN input, 982EN output, 983EN input/output; -4012 Modbus TCP/IP, -6012 EtherNet/IP |
| Inputs | 12 active-low, buffered, common connection; 0 to 35 V DC; about 100 kΩ; TTL-compatible threshold, about 100 mV hysteresis; 5.6 kΩ socketed pull-ups |
| Outputs | 12 open-drain MOSFET; 0 to 35 V DC; 0 to 500 mA per channel continuous; 0.28 Ω max. ON resistance |
| Failsafe | Three selectable modes: off, last state or pre-defined |
| Protocols | EtherNet/IP or Modbus TCP/IP, 10/100 Mbps auto-negotiation; PCCC object for legacy PLCs (EtherNet/IP models) |
| Configuration | Built-in web page |
| Mounting | T rail DIN EN 50022, 35 mm |
| Power supply | 15 to 36 V DC, 2 W |
| Isolation | 1500 V AC for 60 seconds or 250 V AC continuous; 3-way |
| Operating temperature | -25 to 70 °C |
| Approvals | CE; UL and cUL Class I, Division 2, Groups A, B, C, D; EtherNet/IP and Modbus TCP/IP conformance tested |
Figures from the Acromag brochure. Confirm the version and options for your application before ordering.
Download BrochureHow does the Acromag 98xEN work?
Tap a step, or let it run, to follow the signal from the field to the control system.
Step by step:
The 98xEN modules collect on/off signals and drive outputs at a remote point, and talk to the control system over Ethernet. If the network is lost, outputs go to the failsafe state you selected.
Where the Acromag 98xEN is used
Typical applications for this digital to Ethernet module, from the manufacturer's documentation.
- 01Remote monitoringProcess and discrete device states at remote sites.
- 02Motor and contactor statusRemote monitoring of motor loads and contactor status.
- 03Pump and valve controlTank level, pump and valve control.
- 04Utility monitoringPower and water utility monitoring.
- 05Remote switching stationsRemote control switching stations.
- 06Alarm and annunciator systemsProcess shutdown, alarming and annunciator systems.
How the Acromag 98xEN compares
Other signal converters and isolators in our range. The highlighted row is this product. Tap any other name to open its page.
| Product | Type | Signals | Outputs and communication | Supply | Mounting |
|---|---|---|---|---|---|
| Acromag BusWorks XT1540 Ethernet I/O Module | Ethernet I/O | 4 discrete I/O | 8 analogue out; Modbus TCP, EtherNet/IP or PROFINET | 12 to 32 V DC | DIN rail, 22.5 mm |
| Acromag 961EN and 962EN Analogue Input Ethernet I/O | Ethernet I/O | 6 differential current or voltage inputs | Modbus TCP or EtherNet/IP | 15 to 36 V DC | DIN rail |
| Acromag 981EN, 982EN and 983EN Discrete Ethernet I/O | Ethernet I/O | 12 discrete inputs, outputs or both | Modbus TCP or EtherNet/IP | 15 to 36 V DC | DIN rail |
| Datexel DAT 511 Loop-Powered Current Isolator | Loop isolator | 0 to 20 mA | Isolated 0 to 20 mA | Loop powered | DIN rail, 17 mm |
| Datexel DAT 4135 Isolated Universal Signal Converter | Universal converter | RTD, TC, mV, V, mA, resistance | Isolated current or voltage | 18 to 30 Vdc | DIN rail |
| Datexel DAT 4035 Loop-Powered Universal Transmitter | Universal transmitter | RTD, TC, mV, V, mA, resistance | Isolated 4 to 20 mA loop | Loop powered, 10 to 32 Vdc | DIN rail |
From Selection to a Working Signal in Your Control System
A field signal is only as useful as the value that reaches the control room. Proplant PCE handles the configuration, panel work and integration around the device as well as the device itself.
Application review
We check the signals, channel count, network and mounting before recommending a device.
Supply
Instruments and modules from the brands on this page, with the brochure for your engineering file.
Configuration and installation
Ranges, alarms, addresses and network settings set up, then panel building, cabling and termination by our E&I team.
Integration
Mapping into your PLC, SCADA or historian, and testing until the value on screen matches the field.
What to tell us so we can recommend a device
Tick off what you already know. We will check the Acromag 98xEN against your application, or suggest a better fit from our range.
Acromag 98xEN FAQ
What is the difference between the 981EN, 982EN and 983EN?
The 981EN has 12 discrete inputs, the 982EN 12 discrete outputs, and the 983EN 12 channels that work as inputs or outputs.
Which protocols do they support?
Modbus TCP/IP on the -4012 models and EtherNet/IP on the -6012 models, which also have a PCCC object for legacy PLCs.
How much current can the outputs switch?
Up to 500 mA per channel continuous, at 0 to 35 V DC.
What happens if the network is lost?
Outputs go to one of three selectable failsafe states: off, last state or a pre-defined state.
Do they need software?
No. They are configured from a built-in web page.
Can Proplant PCE help me choose the right automation device?
Yes. Send us the signals, channel count, network and mounting, and our team will recommend a suitable device and set it up for your system.
Let's Discuss Your Automation Project
Tell us what signals you need to bring in, where the device sits and what system it reports to. We will come back with a recommendation and the brochure.