Datexel DAT 511 Self-Powered 0 to 20 mA Current Loop Isolator
A passive current loop isolator that takes its power from the measurement loop and reproduces the input current as an isolated output of the same value, with 3000 Vac isolation.

Key Features of the Datexel DAT 511
Passive isolation
Reproduces the 0 to 20 mA input as an isolated 0 to 20 mA output of the same value.
No supply needed
Powered by the measurement loop, with a maximum voltage drop of 3 Vdc on the input.
High isolation
3000 Vac, 50 Hz for 1 minute between input and output.
Accuracy
Transmission error ±0.25 % of full scale; thermal drift 0.02 % of full scale per °C.
Load capability
Output load 0 to 700 Ω, with a response time of 20 ms.
Compact
64 x 62 x 17 mm, about 60 g, on EN 50022 or EN 50035 DIN rail.
Datexel DAT 511 Technical Specifications
Tap a group to filter the loop powered isolator specifications, or show them all.

- 3000 VacIsolation1 min
- ±0.25 %Transmission errorof full scale
- 700 ΩMax. output load
- 20 msResponse time
| Specification | Details |
|---|---|
| Input | 0 to 20 mA, maximum 50 mA |
| Accuracy | Transmission error ±0.25 % of f.s.; load influence ±0.085 % of f.s. / 100 Ω; thermal drift 0.02 % of f.s. / °C |
| Response time | 20 ms |
| Output | 0 to 20 mA, load 0 to 700 Ω |
| Mounting | DIN rail, EN 50022 and EN 50035 |
| Dimensions and weight | 64 x 62 x 17 mm; about 60 g |
| Voltage drop | Maximum 3 Vdc on the input loop |
| Isolation | 3000 Vac, 50 Hz, 1 min |
| Operating temperature | 0 to 55 °C |
| EMC and marking | CE; immunity EN 61000-6-2, emission EN 61000-6-4 |
Figures from the Datexel brochure. Confirm the version and options for your application before ordering.
Download BrochureHow does the Datexel DAT 511 work?
Tap a step, or let it run, to follow the signal from the field to the control system.
Step by step:
Where two systems share a signal, or ground loops upset a reading, the DAT 511 breaks the electrical connection while passing the same current through. It needs no power wiring of its own.
Where the Datexel DAT 511 is used
Typical uses for this loop powered isolator, based on what it does.
- 01Ground loop problemsBreaking the connection where earth differences upset a reading.
- 02Sharing a signalPassing one 4 to 20 mA signal safely to a second system.
- 03Panels without spare supplyIsolation where no extra supply is available.
How the Datexel DAT 511 compares
Other signal converters and isolators in our range. The highlighted row is this product. Tap any other name to open its page.
| Product | Type | Signals | Outputs and communication | Supply | Mounting |
|---|---|---|---|---|---|
| Acromag BusWorks XT1540 Ethernet I/O Module | Ethernet I/O | 4 discrete I/O | 8 analogue out; Modbus TCP, EtherNet/IP or PROFINET | 12 to 32 V DC | DIN rail, 22.5 mm |
| Acromag 961EN and 962EN Analogue Input Ethernet I/O | Ethernet I/O | 6 differential current or voltage inputs | Modbus TCP or EtherNet/IP | 15 to 36 V DC | DIN rail |
| Acromag 981EN, 982EN and 983EN Discrete Ethernet I/O | Ethernet I/O | 12 discrete inputs, outputs or both | Modbus TCP or EtherNet/IP | 15 to 36 V DC | DIN rail |
| Datexel DAT 511 Loop-Powered Current Isolator | Loop isolator | 0 to 20 mA | Isolated 0 to 20 mA | Loop powered | DIN rail, 17 mm |
| Datexel DAT 4135 Isolated Universal Signal Converter | Universal converter | RTD, TC, mV, V, mA, resistance | Isolated current or voltage | 18 to 30 Vdc | DIN rail |
| Datexel DAT 4035 Loop-Powered Universal Transmitter | Universal transmitter | RTD, TC, mV, V, mA, resistance | Isolated 4 to 20 mA loop | Loop powered, 10 to 32 Vdc | DIN rail |
From Selection to a Working Signal in Your Control System
A field signal is only as useful as the value that reaches the control room. Proplant PCE handles the configuration, panel work and integration around the device as well as the device itself.
Application review
We check the signals, channel count, network and mounting before recommending a device.
Supply
Instruments and modules from the brands on this page, with the brochure for your engineering file.
Configuration and installation
Ranges, alarms, addresses and network settings set up, then panel building, cabling and termination by our E&I team.
Integration
Mapping into your PLC, SCADA or historian, and testing until the value on screen matches the field.
What to tell us so we can recommend a device
Tick off what you already know. We will check the Datexel DAT 511 against your application, or suggest a better fit from our range.
Other automation products to consider
Datexel DAT 511 FAQ
What is the Datexel DAT 511?
A passive, self-powered current loop isolator that reproduces a 0 to 20 mA input as an isolated output of the same value.
Does it need a power supply?
No. It takes its power from the measurement loop, with a maximum input voltage drop of 3 Vdc.
How much isolation does it give?
3000 Vac, 50 Hz for 1 minute.
What load can it drive?
Up to 700 Ω on the output.
How accurate is it?
Transmission error is ±0.25 % of full scale.
Can Proplant PCE help me choose the right automation device?
Yes. Send us the signals, channel count, network and mounting, and our team will recommend a suitable device and set it up for your system.
Let's Discuss Your Automation Project
Tell us what signals you need to bring in, where the device sits and what system it reports to. We will come back with a recommendation and the brochure.