ACS Thermocont TS4S Electronic Temperature Switch with LED Display
An all-in-one electronic temperature switch with a bright LED display, two PNP switch outputs and an optional 4 to 20 mA signal, for monitoring, control and continuous measurement in gases, vapours, liquids and dusts.

Key Features of the Thermocont TS4S
Pt100 class A sensor
A long-term stable Pt100 class A resistance sensor to DIN EN 60751 measures the process temperature.
Self-supervision and drift alarm
The type D version adds a semiconductor sensor alongside the Pt100.
The two are monitored against each other, and drift is reported as soon as it passes the set limit, without waiting for a scheduled calibration.
LED display and keys
A high-brightness digital LED display, function LEDs and a 3-key keyboard with tactile feedback.
The enclosure and display can be rotated.
Switch and analogue outputs
PNP switch outputs up to 200 mA, current limited and short-circuit protected, and a 4 to 20 mA output, through an M12x1 plug.
Front-flush sealing
Dead-space-free front-flush O-ring process connections in FPM (Viton) or FDA-listed EPDM suit viscous or contaminated media.
Hygienic and robust
Wetted parts in stainless steel 1.4404/316L or 1.4571/316Ti with Ra < 0.8 µm.
CIP and SIP capable, with a captive laser-marked type label.
Thermocont TS4S Technical Specifications
Tap a group to filter the temperature switch specifications, or show them all.

- -99.9 to +500 °CMeasuring rangetype S, range code 3
- ≤ 100 barProcess pressuredepends on type
- 2x PNP + 4 to 20 mAOutputsdepends on output code
- IP65 / IP67ProtectionEN/IEC 60529
| Specification | Details |
|---|---|
| Measuring system | S: Pt100 class A resistance sensor; D: Pt100 class A plus semiconductor sensor with self-supervision |
| Measuring ranges | -50 to +200 °C (type S); -99.9 to +500 °C (type S); -50 to +175 °C (type D) |
| Characteristic deviation, display and switch | ≤ ±0.6 % FS |
| Characteristic deviation, current output | ≤ ±0.9 K at ±100 °C |
| Self-supervision (type D) | Display and switch ≤ ±0.2 K; current output ≤ ±0.4 K; drift monitoring ≤ ±0.2 K |
| Long-term drift | ≤ ±0.1 % FS per year |
| Temperature deviation | Display and switch ≤ ±0.003 % FS/K; current output ≤ ±0.008 % FS/K |
| Output options | A: 2x switch PNP; B: 1x switch PNP + 4 to 20 mA; C: 2x switch PNP + 4 to 20 mA; D: 1x switch PNP + 4 to 20 mA, Desina-conformal |
| Switch output | PNP to +L, 0 to ≤ 200 mA, current limited, short-circuit protected |
| Analogue output | 4 to 20 mA, operating range 3.9 to 21 mA (min. 3.8 mA, max. 22 mA) |
| Max. load | ≤ (US - 10.5 V) / 20 mA |
| Display | High-brightness digital LED display, function LEDs, 3-key keyboard; rotatable enclosure and display |
| Electrical connection | M12x1 plug, 4-wire (types A, B, D) or 5-wire (type C) |
| Process pressure | ≤ 20 bar, ≤ 100 bar or ≤ 50 bar, depending on type |
| Process connection | Compression fitting; G½" B or G¼" B to ISO 228-1; G½" front-flush with FPM or EPDM O-ring |
| Sensor tube | CrNi steel Ø6, Ø8 or Ø10 mm, reduced tips available; length L1 up to 2000 mm |
| Neck tube | None, or standard L2 = 100 mm (up to 200 mm) |
| Wetted materials | Stainless steel 1.4404/316L or 1.4571/316Ti, Ra < 0.8 µm; gaskets FPM (Viton) and/or EPDM (FDA-listed) |
| Supply voltage | 10.5 to 35 VDC, reverse polarity protected |
| Supply current | ≤ 60 mA (analogue output max. 22.5 mA) |
| Start-up time | ≤ 1 ms |
| Ambient temperature | -40 to +85 °C |
| Protection class | IP65 / IP67 (EN/IEC 60529) |
| Housing materials | Neck tube and terminal enclosure CrNi steel; display cover PES; connector PUR |
Figures from the ACS-Control-System brochure. Confirm the version and options for your application before ordering.
Download BrochureHow does the Thermocont TS4S work?
Tap a step, or let it run, to follow the signal from the process to the control system.
Step by step:
The TS4S switches a pump, heater or alarm directly when the temperature crosses a set point, and can send the measured value to the control system at the same time. On the self-supervising version, the second sensor checks the Pt100 continuously.
Where the Thermocont TS4S is used
Typical applications for this temperature switch, from the manufacturer's documentation.
- 01Machinery and plant engineeringTemperature monitoring and switching on machines and plant equipment.
- 02Hydraulic and pneumatic systemsOil and system temperature switching on hydraulic power units.
- 03Air-conditioning and refrigerationTemperature control points in cooling and air-handling systems.
- 04Process industryMonitoring and control of process temperatures in gases, vapours, liquids and dusts.
- 05Environmental technologyTemperature measurement on environmental and treatment plant.
- 06Paint and coating industryFront-flush versions for viscous and contaminated media.
How the Thermocont TS4S compares
The highlighted row is this instrument. Tap any other name to open its page.
| Instrument | Type | Input | Output | Supply | Mounting |
|---|---|---|---|---|---|
| ACS Thermocont TS4S Temperature Switch | Temperature switch | Pt100 class A, built in | 2x PNP switch, 4 to 20 mA option | 10.5 to 35 VDC | G½" or G¼" thread, compression fitting |
| Datexel DAT 1066 Head-Mount Temperature Transmitter | Head-mount transmitter, isolated | RTD, thermocouple, mV, resistance | 4 to 20 mA | 7 to 32 Vdc | DIN B head, DIN rail kit |
| NOVUS TxBlock-USB and TxRail-USB Temperature Transmitters | Head-mount or DIN rail transmitter | Thermocouple, Pt100, Pt1000, NTC, mV | 4 to 20 mA; 0 to 10 V on TxRail-USB | 8 to 35 Vdc (TxBlock-USB) | Sensor head or DIN rail |
| NOVUS TxIsoPack-USB Isolated Temperature Transmitter | Head-mount transmitter, isolated | Pt100, thermocouple, mV | 4 to 20 mA or 20 to 4 mA | 12 to 35 Vdc | Sensor head |
| NOVUS TxMini Compact Temperature Transmitter | Compact transmitter | Pt100 or Pt1000, 3-wire | 4 to 20 mA | 8 to 35 Vdc | M12 or DIN 43650 connector |
| NOVUS RHT-Air Wireless Temperature and Humidity Transmitter | Wireless transmitter | Built-in temperature and humidity sensors | Wireless to AirGate-Modbus | Battery or 10 to 35 Vdc | Wall mount or probe extension |
From Selection to a Working Signal in Your Control System
A temperature reading is only as useful as the signal that reaches the control room. Proplant PCE handles the steps around the instrument as well as the instrument itself.
Application review
We check the process temperature, sensor type, mounting and the signal your control system needs before recommending a transmitter.
Supply
Transmitters, switches and sensors from the brands on this page, with the brochure for your engineering file.
Configuration and installation
Range, sensor type and failure behaviour set before delivery, then mounting, cabling and termination by our E&I team.
Integration
Loop wiring and scaling in your PLC or SCADA, so the temperature on screen matches the process.
What to tell us so we can recommend an instrument
Tick off what you already know. We will check the Thermocont TS4S against your conditions, or suggest a better fit from our range.
Other temperature instruments to consider
Thermocont TS4S FAQ
What is the Thermocont TS4S?
An electronic temperature switch from ACS-Control-System with a Pt100 class A sensor, an LED display, PNP switch outputs and an optional 4 to 20 mA signal.
What temperature range does the TS4S cover?
The type S version is available for -50 to +200 °C or -99.9 to +500 °C. The self-supervising type D covers -50 to +175 °C.
What outputs are available?
Two PNP switch outputs, one switch output with 4 to 20 mA, two switch outputs with 4 to 20 mA, or a Desina-conformal version with one switch and 4 to 20 mA.
What does self-supervision mean on the TS4S?
On the type D version a semiconductor sensor works alongside the Pt100. The two readings are monitored against each other, and the unit signals when drift passes the set limit.
Can the TS4S be used in hygienic applications?
The wetted parts are stainless steel with Ra < 0.8 µm, front-flush O-ring connections are available in FDA-listed EPDM, and the unit is CIP and SIP capable.
Can Proplant PCE help me choose the right temperature transmitter?
Yes. Send us the sensor type, temperature range, mounting and the output your control system needs, and our team will recommend a suitable instrument.
Let's Discuss Your Temperature Application