NOVUS LoopView 4 to 20 mA Loop-Powered Indicator
A 4 to 20 mA indicator powered by the loop itself. It plugs between a sensor and its valve-type connector, so a field transmitter gets a local display with no extra supply.

Key Features of the NOVUS LoopView
Loop powered
Takes its power from the two-wire 4 to 20 mA loop, with a voltage drop below 2.5 V at 4 mA and below 3 V at 20 mA.
Sandwich assembly
Fits between the sensor and its EN 175301-803 (formerly DIN 43650) valve-type connector.
4-digit LED display
Red LED, -1999 to 9999, scaled to engineering units.
Accuracy
0.1 % of span, 0.003 % per °C thermal deviation and 16-bit resolution.
Simple set-up
Two front keys with password protection; settings kept in non-volatile memory.
Rugged
IP65 and NEMA 4X, -40 to 85 °C, 65 x 45 x 45 mm.
NOVUS LoopView Technical Specifications
Tap a group to filter the loop powered indicator specifications, or show them all.

- 0.1 %Accuracyof span
- < 3 VVoltage dropat 20 mA
- -40 to 85 °COperating temperature
- IP65ProtectionNEMA 4X
| Specification | Details |
|---|---|
| Input | Two-wire 4 to 20 mA passive loop |
| Accuracy | 0.1 % of span; thermal deviation 0.003 % per °C |
| Resolution | 65535 levels (16 bits) |
| Display | 4-digit red LED, -1999 to 9999 |
| Configuration | Two front keys, password protected; non-volatile memory |
| Connection | Valve-type connector EN 175301-803 (formerly DIN 43650), male and female |
| Dimensions | 65 x 45 x 45 mm |
| Power | Loop powered; voltage drop below 2.5 V at 4 mA and below 3 V at 20 mA |
| Operating temperature | -40 to 85 °C |
| Protection | IP65, NEMA 4X |
Figures from the NOVUS Automation brochure. Confirm the version and options for your application before ordering.
Download BrochureHow does the NOVUS LoopView work?
Tap a step, or let it run, to follow the signal from the field to the control system.
Step by step:
LoopView sits in series with the loop, so it needs no wiring of its own. Operators see the value at the instrument while the same signal carries on to the control system.
Where the NOVUS LoopView is used
Typical applications for this loop powered indicator, from the manufacturer's documentation.
- 01PressureLocal reading on pressure transmitters.
- 02Differential pressureFilter and flow element readings at the instrument.
- 03FlowLocal display on flow transmitters.
- 04pHA local value on pH loops.
- 05TemperatureLocal display on temperature transmitters.
- 06AccelerationA local reading on vibration and acceleration loops.
How the NOVUS LoopView compares
Other digital indicators and controllers in our range. The highlighted row is this product. Tap any other name to open its page.
| Product | Type | Signals | Outputs and communication | Supply | Mounting |
|---|---|---|---|---|---|
| ACS DPA Digital Display Unit | Digital display unit | 0/4 to 20 mA, 0 to 10 V | Isolated analogue out, up to 4 relays, Bluetooth or USB | 18 to 36 V DC or 186 to 253 VAC | Panel, field or DIN rail |
| NOVUS N1050 PID Temperature Controller | PID controller | Thermocouple J, K, T, S; Pt100 | SSR pulse, relays, USB, optional Modbus RTU | 100 to 240 Vac/dc | Panel, 48 x 48 mm |
| NOVUS N1040i Process Indicator | Process indicator | Thermocouple, Pt100, mA, mV, V | 2 relays, optional retransmission and RS485 | 100 to 240 Vac or 48 to 240 Vdc | Panel, 48 x 48 mm |
| NOVUS N1540 Universal Indicator | Universal indicator | Thermocouple, Pt100, mA, mV, V | 2 relays, USB, optional Modbus RTU | 100 to 240 Vac/dc | Panel, 96 x 48 mm |
| NOVUS LoopView Loop-Powered Indicator | Loop-powered indicator | 4 to 20 mA loop | Local LED display | Loop powered | On the sensor connector |
From Selection to a Working Signal in Your Control System
A field signal is only as useful as the value that reaches the control room. Proplant PCE handles the configuration, panel work and integration around the device as well as the device itself.
Application review
We check the signals, channel count, network and mounting before recommending a device.
Supply
Instruments and modules from the brands on this page, with the brochure for your engineering file.
Configuration and installation
Ranges, alarms, addresses and network settings set up, then panel building, cabling and termination by our E&I team.
Integration
Mapping into your PLC, SCADA or historian, and testing until the value on screen matches the field.
What to tell us so we can recommend a device
Tick off what you already know. We will check the NOVUS LoopView against your application, or suggest a better fit from our range.
Other automation products to consider
NOVUS LoopView FAQ
What is the NOVUS LoopView?
A 4 to 20 mA indicator powered by the loop, which fits between a sensor and its valve-type connector.
Does it need its own power supply?
No. It takes its power from the 4 to 20 mA loop, with a voltage drop below 3 V at 20 mA.
Which connector does it fit?
The EN 175301-803 valve-type connector, formerly DIN 43650.
How accurate is it?
0.1 % of span, with 16-bit resolution.
Can it be used outdoors?
It is rated IP65 and NEMA 4X, for -40 to 85 °C.